Where Are Fire Doors Required? A Room-by-Room UK Guide
Two sets of rules decide it
Whether a particular opening needs a fire door comes from two places:
- Building Regulations — Approved Document B. Applies when a building is built, extended or materially altered. It sets out where fire doors must be provided.
- The Regulatory Reform (Fire Safety) Order 2005, informed by your fire risk assessment. Applies for the life of any non-domestic premises and the common parts of residential blocks, and can require fire doors where the risk assessment identifies the need.
If the two ever appear to disagree, the fire risk assessment for the building in use is what enforcement will look at.
In a house
| Location | Fire door required? | | --- | --- | | Doors from habitable rooms onto the stairway in a home with a floor over 4.5 m above ground (usually three storeys or a loft conversion) | Yes — FD30 | | Door between an integral garage and the house | Yes — FD30, self-closing | | Doors in a standard two-storey house | Normally no | | Door from a habitable room into an open-plan kitchen/lounge arrangement | Depends on the approved fire strategy for the layout | | Cupboard under a protected stair | Yes where it opens into the protected stairway |
The loft conversion case is the one that catches most homeowners: adding a third storey creates a protected stairway, and that changes the doors on the floors below as well as the new one.
In a flat or block of flats
| Location | Typical requirement | | --- | --- | | Flat entrance door onto a communal area | FD30S doorset, self-closing | | Communal corridors and lobbies | FD30S, self-closing | | Protected stairways | FD30S / FD60S per the fire strategy | | Riser cupboards, meter cupboards, bin and refuse stores | FD30 / FD60, "keep locked" | | Doors within a flat where the flat has more than one storey | FD30 to the internal protected route |
In buildings above 11 m, the Fire Safety (England) Regulations 2022 require quarterly checks of communal fire doors and annual best-endeavours checks of flat entrance doors.
In an HMO
House in multiple occupation licensing conditions typically require:
- FD30S to each letting bedroom off the escape route, self-closing.
- FD30S to kitchens and other higher-risk rooms.
- Protected escape route from every letting to a final exit.
Exact conditions are set by your local housing authority, so check the licence rather than assuming. More detail in our HMO fire door requirements guide.
In commercial and public buildings
- Protected stairways and lobbies
- Compartment walls between fire compartments (door rating must match the wall)
- Plant rooms, boiler rooms, switch rooms, sprinkler rooms
- Service risers and ducts
- Refuse stores
- Corridors forming part of an escape route
- Any room the fire strategy identifies as higher risk
Where a fire door is not required
- Most doors in a standard two-storey house
- Final exit doors leading directly to a place of safety — these must be easily openable in the direction of escape, but usually need no fire rating
- Internal doors within a single-storey flat, unless the fire strategy says otherwise
Fitting fire doors where they are not needed is not a compliance win. Over-specification adds cost, adds weight, and can create Approved Document M accessibility problems with opening forces.
The rating has to match the wall
Whatever the location, the door must match the fire resistance of the construction around it. An FD30 door in a 60-minute compartment wall is a failure, and so is an FD60 door hung in a frame that was only ever tested for FD30.
Not sure what your building needs?
A competent fire risk assessment answers the question properly for a building in use, and a fire door survey tells you whether what is installed matches. Stark Contracts provides both across Lincolnshire and the East Midlands — see fire risk assessments and fire door inspection, or call 01522 775570.