Intumescent Strips and Cold Smoke Seals in Ruskington Fire Doors: The 60-Second Guide

What Intumescent and Smoke Seals Actually Do

An intumescent strip expands to roughly 8× its cold volume at around 200°C, sealing the gap between the leaf and the frame with a rigid char that resists flame passage. A cold smoke seal is a brush or fin that closes the same gap at ambient temperatures, blocking smoke movement before the fire builds.

Together they are the only reason a fire door with a 3mm perimeter gap can hold back fire for 30 or 60 minutes.

Why Ruskington Doors Fail Seal Checks

In {C} inspections we routinely find:

  1. Painted-over seals — layer after layer of gloss paint means the seal cannot expand freely

  2. Snapped or chipped strips — usually from door slams or trolley collisions

  3. Wrong-sized strips — 15×4mm fitted where the tested door needs 20×4mm

  4. Missing sections — strip fitted only to head and jambs, gaps at corners

  5. Cold smoke brushes worn flat — no longer contacting the leaf

The Cost of Replacement in Ruskington

Intumescent strip replacement per door: £45–£75 supplied and fitted. Full FD30S seal kit (intumescent + smoke brush): £65–£95. A full doorset replacement is £795+. The economics are obvious.

Certification Matters

Not all intumescent strips are equal. On Ruskington jobs we specify seals from BM TRADA-listed suppliers — Lorient, IFC Certification and Envirograf are the mainstream choices. Off-brand strips from generic suppliers may not carry the test evidence to preserve BS 8214 compliance.

Call 01522 775570 for seal replacement across your Ruskington portfolio.

Related reading

remedial works · fire door maintenance · fire doors in Ruskington