Fire Door Letterboxes, Cat Flaps and Locks — What's Actually Allowed

The principle

Every hole cut in a fire door has to be tested as part of the doorset or fitted with a certified, fire-rated component that has been third-party tested in a like-for-like assembly. The moment an untested aperture is cut, the door's BS 476-22 or BS EN 1634-1 fire test result no longer applies and the certification is void.

That is the rule that catches almost every flat-entrance door retrofit we inspect.

Letterboxes

  • Plastic or unrated metal letterboxes are not permitted on certified fire doors. They melt, drop out and leave an open aperture for smoke and flames within the first 5–10 minutes of a fire.
  • Certified fire-rated letterplates (e.g. UAP Fire-Rated, ERA Fortress FD30, Avocet Affinity) are tested to BS EN 1634-1 alongside a 44 mm FD30 leaf and include an intumescent liner that seals the aperture when heat hits it. These are the only letterplates that should appear on a flat entrance door under the Fire Safety (England) Regulations 2022.
  • Position matters — most certified letterplates have a tested location (typically mid-leaf, on the lockset side); fitting one in the wrong position or upside-down voids the certification.
  • Anti-arson cowls and internal smoke pouches are not a substitute for a certified letterplate; they are an addition.

Cat flaps and pet doors

There is no UK-certified fire-rated cat flap on the market that maintains FD30 integrity on a flat entrance door. Cutting a cat flap into a certified flat entrance door voids the rating — full stop. For HMOs, blocks of flats and any door protecting an escape route, the answer is no.

On internal doors in a single-occupancy house that are not on a protected escape route (e.g. a utility room door), a cat flap is a building decision rather than a fire door decision — but if the door was originally specified as FD30, it no longer is one once the flap is fitted.

Locks, latches and thumb-turns

  • Use a CE/UKCA-marked fire-rated mortice latch or sashlock (BS EN 12209 plus a fire-test certificate). Standard high-street mortice locks are not fire-tested.
  • Multi-point locks on flat entrance doors must be fire-rated assemblies — most domestic uPVC-style multi-points are not.
  • Thumb-turns are required on the inside of every flat entrance door so occupants can escape without a key (Fire Safety (England) Regulations 2022). Use a fire-rated euro cylinder with thumb-turn.
  • Electric strikes, mag-locks and access control must be fire-rated, fail-safe on power loss, and wired into the fire alarm via a certified relay so they release on activation.

Door viewers (spy-holes)

Use a fire-rated 200° door viewer with an intumescent liner — these are tested to BS EN 1634-1 and are widely available. A standard brass viewer is not fire-rated and burns out of the aperture in minutes.

What to do if it's already been cut

If a flat entrance door has had a non-rated letterplate, cat flap or lock retrofitted, the door is non-compliant and the building's responsible person is exposed under the Fire Safety Order 2005 — which carries fines up to unlimited amounts on indictment. The options are:

  1. Replace the door with a new pre-hung FD30S doorset — almost always the cheapest defensible route on a flat entrance door.
  2. Block and re-test the aperture — possible on a workshop door, rarely defensible on a fitted door because the patch is not part of the original tested assembly.

What we do

Stark Contracts fits certified fire-rated letterplates, viewers, thumb-turns and access control as part of every flat entrance door installation, and our remedial works service covers retrofit upgrades on existing doors where the rest of the door is still serviceable.