Why Must Fire Doors Be Kept Shut? (And When You Can Legally Hold Them Open)

The one-line answer

A fire door only resists fire when it is closed. Held open, it is an open hole in a fire-resisting wall, and the compartment it was built to protect no longer exists.

What is actually happening in those 30 minutes

A closed FD30 doorset does three jobs at once:

  1. Holds back flame for at least 30 minutes, giving people time to escape and the fire service time to arrive.
  2. Restricts smoke, which is what actually harms people. Most fire fatalities in the UK are caused by smoke inhalation, not burns. Cold smoke seals on an FD30S door only work when the leaf is against the stop.
  3. Preserves compartmentation, keeping the fire in one part of the building so the escape routes elsewhere stay usable.

Prop that door open and all three fail at once. A protected stairway with one wedged door can fill with smoke in a couple of minutes.

The legal position

Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person must ensure fire safety measures — including fire doors — are maintained in efficient working order and in good repair. A fire door routinely held open with a wedge, an extinguisher or a bin is not in efficient working order. Breaches are prosecutable, with fines up to unlimited amounts on indictment and, in serious cases, custodial sentences.

In blocks of flats, the Fire Safety (England) Regulations 2022 add specific duties for buildings over 11 m: quarterly checks of communal fire doors, annual checks of flat entrance doors, and information for residents on the importance of keeping fire doors shut and not tampering with self-closers.

Signage is also a duty. "Fire door keep shut" signs are required on both faces of self-closing fire doors on escape routes, and "Fire door keep locked" on cupboards, risers and stores.

Why people wedge doors — and what to do instead

Doors get wedged for practical reasons: moving stock, ventilation in summer, wheelchair or trolley access, a closer set far too heavy, or a corridor that feels institutional when every door is shut. Telling people to stop rarely works on its own. Fixing the underlying cause does.

Check the closer first. If the door is genuinely too heavy, that is not just a fire problem, it is an accessibility problem. Approved Document M expects an opening force of no more than 30 N from the closed position through the first 30 degrees of swing, and no more than 22.5 N from 30 to 60 degrees, measured at the leading edge. A correctly specified and adjusted closer will meet that and still close and latch reliably. Winding the closer down until the door will not latch is not the answer.

Then fit a compliant hold-open device. There are three legitimate options:

| Device | Standard | How it works | | --- | --- | --- | | Electromagnetic hold-open device | BS EN 1155 | Holds the door open on a magnet; releases on the fire alarm signal | | Free-swing door closer | BS EN 1155 | The door swings freely in normal use and becomes self-closing on alarm | | Acoustic release device | Must be assessed carefully | Battery-powered unit that listens for the alarm sounder and releases |

Devices that hold a fire door open must be interfaced with the fire detection and alarm system in accordance with BS 7273-4, and must fail safe — releasing the door on alarm, on power failure and on system fault. They also need to be included in your routine testing regime.

Acoustic devices can be appropriate in some small premises but are not a universal substitute for a properly interfaced system; take advice before relying on them in a sleeping-risk building.

What is never acceptable: wedges, hooks, cabin hooks, tied-back closers, disconnected closer arms, furniture, fire extinguishers used as door stops.

Practical steps for responsible persons

  1. Walk the building at a busy time, not a quiet one, and note every door being held open.
  2. For each one, record why. Ventilation, access, weight or habit each need a different fix.
  3. Test the closers and check the opening forces against the accessibility limits.
  4. Where holding a door open is genuinely needed, specify a BS EN 1155 device interfaced to BS 7273-4 — and add it to your test schedule.
  5. Confirm signage is present on both faces of self-closing doors on escape routes.
  6. Record everything. Under enforcement, the evidence you can produce matters as much as the condition of the doors.