Internal Fire Doors: The Complete UK Guide (2026)
What is an internal fire door?
An internal fire door is a door assembly tested to hold back fire and hot gases for a defined period — normally 30 minutes (FD30) or 60 minutes (FD60). It is not simply a heavier door. The fire resistance comes from the whole assembly working together: the leaf, the frame, the intumescent seals, the hinges, the closer, the latch and the way it was installed.
That distinction matters more than anything else on this page. You cannot buy a "fire door" as a leaf on its own and assume compliance. What is tested, certified and inspected is the doorset — leaf plus frame plus ironmongery, installed in accordance with the manufacturer's installation instructions.
Where the law requires internal fire doors
Requirements come from two directions.
Building Regulations (Approved Document B) set out where fire doors must be provided when a building is built or altered:
| Situation | Typical requirement | | --- | --- | | Dwelling with a floor over 4.5 m above ground (usually three storeys or a loft conversion) | FD30 to every habitable room opening onto the protected stairway | | Door between an integral garage and a house | FD30, self-closing | | Flat entrance door | FD30S doorset | | Protected corridors and stairways in blocks of flats | FD30S, self-closing | | Compartment walls in commercial buildings | FD60 where the wall requires 60 minutes | | Plant rooms, risers, bin stores, boiler rooms | Rating to match the enclosing construction |
The Regulatory Reform (Fire Safety) Order 2005 then applies for the life of the building. It places a continuing duty on the responsible person to keep fire doors in effective working order. Breaches are prosecutable, with fines up to unlimited amounts on indictment.
FD30 or FD60 — how to choose
You do not choose the rating; the building does. The fire door must match the fire resistance of the wall it sits in, as determined by the building's fire strategy or fire risk assessment.
- FD30 — 30 minutes' integrity. The most common rating: dwellings, flat entrance doors, HMO bedrooms, offices, general escape routes.
- FD60 — 60 minutes' integrity. Used in compartment walls, plant and boiler rooms, service risers, refuse stores, and taller or higher-risk buildings.
- The "S" suffix (FD30S, FD60S) means the door is additionally fitted with cold smoke seals. Anywhere smoke control matters — flat entrance doors, protected corridors, bedrooms in sleeping accommodation — the S rating is normally required.
What a compliant internal fire door looks like
When our surveyors inspect a door to BS 8214:2026, these are the items recorded:
- Certification and traceability. A third-party certification label or plug (BM TRADA Q-Mark, Certifire or equivalent) on the top or hanging edge, with a legible reference. No evidence means no compliance, however good the door looks.
- Gaps. Around 3 mm at the head and jambs, with a tolerance of roughly ±1 mm. The threshold gap must follow the certification — typically no more than 10 mm to a non-combustible floor finish, and less where smoke seals are required.
- Intumescent strips and smoke seals. Continuous, correctly sized, fitted to the edge specified in the certification, undamaged and not painted over.
- Hinges. Normally three CE/UKCA-marked hinges to BS EN 1935 Grade 13, correctly bedded, with all screws present and of the specified length.
- Self-closing device. Tested to BS EN 1154 where required, closing the door fully from any angle and engaging the latch every time.
- Ironmongery and penetrations. Locks, latches, letterplates, vision panels and closers must all be fire-rated and part of the tested specification. Any unauthorised hole is a failure.
- Signage. "Fire door keep shut" on both sides where relevant, or "Fire door keep locked" for cupboards and risers.
- Frame and Architraves. Correctly fixed, fully packed with the specified material, with no combustible expanding foam used as a fire-stopping product unless it is part of the tested specification.
Accessibility — Approved Document M
Fire doors on accessible routes must also satisfy Approved Document M. The two points that most often conflict with fire door specification are:
- Opening force. The force required to open the door should not exceed 30 N from the closed position through the first 30 degrees of swing, and 22.5 N from 30 to 60 degrees, measured at the leading edge. Over-specified closers routinely fail this.
- Clear effective width. The clear opening must suit the approach and the building type. Fitting a self-closer to an already narrow doorway can push a door below the required width.
The answer is not to weaken the closer or remove it. It is to specify a door, closer and frame combination that meets both duties — which is a design decision, not a site fix.
Common mistakes we are called out to fix
- Uncertified leaves hung in certified frames (or the reverse). The assembly is only as good as its weakest tested component.
- Painted-over intumescent strips. Paint can prevent the strip expanding correctly.
- Wrong screws. Short or plated screws in fire-rated hinges are one of the most frequent failures we log.
- Excessive threshold gaps after new flooring is laid over the original finish.
- Retro-fitted vision panels cut on site, outside the tested specification.
- Closers wound down because occupants found the door too heavy — creating both a fire and an accessibility failure.
Repair or replace?
Not every defect requires a new doorset. Damaged seals, worn hinges, failed closers, missing signage and small areas of damage within the tolerances of the manufacturer's instructions can normally be remediated. Structural damage to the leaf, an uncertified door, or a door with unrecorded modifications generally cannot be brought back into certification and should be replaced with a certified doorset.
Getting it checked