What We Check During a Fire Door Survey in Lincoln
What We Check During a Fire Door Survey
When our BM TRADA certified inspectors carry out a fire door survey in Lincoln or across Lincolnshire, we follow a comprehensive checklist that covers every critical element.
Our Inspection Checklist
Door Leaf
- Certification label present and legible
- No holes, cracks or structural damage
- Correct thickness for rating
- No unauthorised modifications
Gaps & Tolerances
- Head gap: 3mm ±1mm
- Side gaps: 3mm ±1mm
- Threshold gap: maximum 8mm (or as specified)
- Consistent gaps around the full perimeter
Intumescent Strips & Smoke Seals
- Present on all required edges
- Correct specification for the door rating
- Not painted over or damaged
- Properly recessed into grooves
Ironmongery
- Minimum 3 hinges, CE-marked and fire-rated
- Self-closing device fitted and functioning
- Latch/lock operating correctly
- Handles secure
Frame
- Securely fixed to structure
- No damage or gaps between frame and wall
- Intumescent strips present if required
Glazing
- Fire-rated glass verified
- Correct beading system
- No cracks or damage
The Report
After inspection, you receive a detailed report with:
- Individual door assessments with photographs
- Pass/fail/advisory ratings
- Prioritised remedial recommendations
- Cost-effective solutions