Smoke Seals vs Intumescent Strips: What's the Difference and Do You Need Both?

Smoke Seals vs Intumescent Strips: Do You Need Both?

One of the most frequently misunderstood aspects of fire door compliance is the difference between smoke seals and intumescent strips. Many people think they're the same thing. They're not — and most fire doors require both.

Intumescent Strips: Protection Against Fire

Intumescent strips are thin strips of material (typically graphite-based) fitted into a groove around the door edge or frame. They lie dormant at normal temperatures.

In a fire (above approximately 200 degrees C), the intumescent material expands rapidly — up to 10 times its original volume — sealing the gap between the door and frame. This prevents flames and hot gases from passing through.

  • Purpose: Seal gaps against fire
  • Activation: Heat (typically 200+ degrees C)
  • Position: Fitted in a routed groove in the door edge or frame
  • Standard width: 10mm or 15mm depending on specification

Smoke Seals: Protection Against Cold Smoke

Smoke seals (also called brush seals or compression seals) are flexible strips — usually made from neoprene, silicone, or brush fibres — that create a physical barrier against smoke at normal temperatures.

Smoke kills more people in fires than flames. Cold smoke travels quickly through buildings, filling corridors and stairwells before temperatures rise high enough to activate intumescent strips.

  • Purpose: Seal gaps against cold smoke
  • Activation: Always active (physical compression)
  • Position: Fitted alongside intumescent strips, or as a combined intumescent/smoke seal product
  • Also called: "S" suffix on door ratings (e.g., FD30S means fire AND smoke rated)

Do You Need Both?

In most cases, yes.

Under BS 8214:2026 and the Fire Safety (England) Regulations 2022:

  • Flat entrance doors in buildings over 11m must be FD30S — meaning they require BOTH intumescent strips AND smoke seals
  • Communal corridor doors should have smoke seals to prevent smoke spread
  • Stairwell doors should be smoke-sealed to protect vertical escape routes

The "S" designation on a fire door rating indicates that it has been tested for smoke leakage as well as fire resistance.

Combined Products

Many modern intumescent strips incorporate a built-in smoke seal — a flexible fin or brush attached to the intumescent material. These "combo" seals are increasingly common and simplify installation.

When we assemble pre-hung door sets at Stark Contracts, we typically use combined intumescent and smoke seal strips — providing both fire and smoke protection in a single product, factory-fitted in our workshop.

Common Defects We Find

During inspections across Lincoln and the East Midlands:

  • Intumescent strips painted over — paint can prevent expansion in a fire
  • Smoke seals missing entirely — especially on older doors that pre-date "S" rating requirements
  • Wrong size strips — 10mm strips fitted where 15mm was specified in the fire test
  • Strips pulled out — by tenants, decorators, or maintenance staff who didn't know what they were
  • Strips fitted in wrong position — must be in the correct groove as per manufacturer's instructions

What to Check on Your Fire Doors

  1. Look at the edge of the door (hinge side and lock side): are intumescent strips visible in a routed groove?
  2. Are smoke seals present alongside or integrated with the intumescent strips?
  3. Are the strips intact — not painted over, damaged, or missing sections?
  4. Check the top edge too — intumescent protection is required on three edges (not the bottom)