Fire Door Locks, Latches and Ironmongery: What Is Actually Allowed

The rule behind every item on this page

A fire door is certified as a complete assembly. Any item fitted to it — lock, latch, closer, handle, letterplate, spy hole, kick plate, air transfer grille — must either have been part of the tested specification or be separately fire-tested and declared suitable for use on that type of fire door. Every hole cut in the leaf is a potential fire path, and every uncertified item is a defect at inspection.

Latches: what makes the door work

Most fire doors need a latch. Without one, a closer can pull the door up to the frame but nothing holds the leaf tight into the rebate as it distorts and the seals expand.

  • Fire-rated mortice latches and sashlocks should be tested to BS EN 12209 and CE/UKCA marked as suitable for fire door assemblies.
  • Many certifications require intumescent pads or liners in the lock case mortice and behind the forend and strike plate.
  • Strike plates must be steel and fully recessed into the frame, with the recess neatly formed rather than chiselled oversize.
  • A latch that does not engage every time — because of closer adjustment, a dropped leaf or a misaligned keep — is one of the most common single failures on any inspection round.

Bathroom and en-suite doors in dwellings are one of the few common exceptions where a latch may not be required, provided the certification and the fire strategy allow it.

Locks and escape

Security and escape have to coexist. On escape routes:

  • Doors on escape routes must be openable without a key and, ideally, in a single action.
  • BS EN 1125 panic bars and touch bars are used where the public may be present or occupancy is high.
  • BS EN 179 emergency push pads and lever handles are used where occupants are familiar with the building.
  • Thumbturn cylinders, electric locks with fail-safe release, and free-egress deadlocks are all acceptable where specified — provided they are fire-rated and part of the door's evidence.

Bolts, padlocks, hasps and surface-mounted security devices retrofitted to an escape door are enforcement issues as well as fire door defects.

Closers

Self-closing devices must be tested to BS EN 1154 where the door needs to be self-closing. The device has to close the door fully from any opening angle and engage the latch. Spring hinges and rising butts do not satisfy this.

The tension has to be balanced against Approved Document M: no more than 30 N at the leading edge from closed through the first 30 degrees, and 22.5 N from 30 degrees to open. Where a heavy door meets a wheelchair-accessible route, the answer is a correctly sized closer with adjustable backcheck and delayed action, or a BS EN 1155 electromagnetic hold-open device linked to the fire alarm to BS 7273-4 — not a wedge and not a disconnected arm.

Letterplates, spy holes and vision panels

  • Letterplates must be fire-rated with an intumescent liner, sized to the aperture the certification permits, and positioned as tested. Standard hardware-shop letterplates in a flat entrance door are a straightforward failure.
  • Spy holes must be metal-bodied and fire-rated; plastic viewers melt out and leave an open hole.
  • Vision panels can never be cut in on site. See our guide to glazed fire doors and vision panels.

Air transfer grilles and cables

Only intumescent air transfer grilles certified for the door's rating may be fitted, and only where the certification allows an aperture. Cables for access control must pass through certified door loops or concealed transfer devices; a drilled hole with a cable through it destroys the rating. Electric strikes, maglocks and access control furniture all need fire-rated equivalents and a fail-safe release tied to the alarm.

Kick plates, signage and numerals

  • Kick plates must be within the size and fixing method the certification allows, usually bonded or fixed with short screws that do not penetrate deeply into the core, and often limited to a maximum height above the bottom edge.
  • Signage — "Fire door keep shut", "Fire door keep locked shut", "Automatic fire door keep clear" — should be fixed with adhesive rather than screws wherever possible.
  • Screwed-on house numbers and nameplates in flat entrance doors are a frequent avoidable defect.

Getting it right first time

If you are specifying a new doorset, agree the full ironmongery schedule with the manufacturer before the door is made, so every item is within the certification and the leaf is prepared under factory control. If you are maintaining existing doors, treat ironmongery changes as certified work with photographic records, not as general handyman jobs.

Stark Contracts specifies, supplies and fits fire-rated ironmongery as part of installation and remedial packages across the East Midlands and Humber. Call 01522 775570 or email Enquiries@Starkcontracts.co.uk.