Fire Door Ironmongery: Specification Guide for Hinges, Locks and Closers
Fire Door Ironmongery: A Complete Specification Guide
Ironmongery is where most fire door compliance failures happen. A perfectly certified door leaf, hung in a fire-rated frame, with correct intumescent seals — can be rendered non-compliant by a single piece of incorrect ironmongery.
Hinges
Minimum requirement: Three CE-marked, fire-rated hinges per fire door.
Specifications:
- Material: Grade 13 stainless steel (Grade 316 for corrosive environments)
- Size: 102mm x 76mm for standard FD30 doors; 102mm x 102mm for heavier FD60 doors
- Fixing: Must be screw-fixed into the frame — not clipped or push-fit
- Standard: BS EN 1935 (single-axis hinges for doors)
- Fire rating: Must be tested as part of the door assembly
Common mistake: Using two hinges instead of three. This is non-compliant regardless of door weight.
Self-Closing Devices
Every fire door must have a self-closing device that closes the door from any angle into the frame.
Options include:
- Overhead closers — most common, surface-mounted (e.g., Dorma TS 83, GEZE TS 4000)
- Concealed closers — mounted in the door/frame (e.g., Perko Powermatic)
- Floor springs — recessed into the floor (typically commercial applications)
Standard: BS EN 1154 (controlled door closing devices)
Critical point: The closer must be tested with the specific door type. A closer rated for a 40kg door used on a 55kg FD60 door will fail to close it reliably.
Locks and Latches
Fire doors in escape routes must have a latch mechanism that holds the door in the closed position.
- Standard: BS EN 12209 (mechanically operated locks and latches)
- Requirement: The lock/latch must be fire-rated and tested as part of the door assembly
- Escape routes: Must use a thumb-turn or panic hardware on the escape side — never a key-only lock
Common mistake: Fitting a standard domestic 3-lever mortice lock from a DIY store. These are not fire-rated and the body may deform in heat, allowing the door to swing open.
Handles
- Must be non-combustible — typically stainless steel or aluminium
- Must be tested with the door assembly
- Lever handles must return to horizontal (for accessibility and to prevent snagging)
- Rose or backplate fixings must not compromise the door's integrity
Letter Plates (If Required)
Letter plates cut into fire doors create a direct path for fire and smoke. If a letter plate is required:
- Must be a fire-rated intumescent letter plate (e.g., Intumescent Letterbox Protector)
- The intumescent material must be tested as part of the door assembly
- Size restrictions apply — maximum aperture as specified by the door manufacturer's field of application
Our recommendation: Avoid letter plates on fire doors wherever possible. Use communal letterboxes instead.
Viewers / Spyholes
If a door viewer is fitted:
- Must be fire-rated (standard brass viewers are not)
- Must include intumescent protection
- Must be tested as part of the door assembly or within the field of application
Signage
All fire doors in communal areas must display:
- "Fire Door Keep Shut" — on both sides (or one side if a hold-open device is fitted)
- "Fire Door Keep Locked" — if the door is required to be kept locked
Signage must be securely fixed but must not compromise the door's integrity (e.g., screws through the door face into the core can create a fire path).
The Field of Application Rule
Every door manufacturer publishes a field of application document listing exactly which ironmongery has been tested with their door blanks. Using ironmongery outside this list means:
- The fire test evidence no longer applies
- The door's certification is potentially void
- The Responsible Person carries the liability
Our Approach at Stark Contracts
We specify all ironmongery within the manufacturer's field of application and source directly from certified suppliers. Our pre-hung door sets arrive on site with every piece of ironmongery factory-fitted and documented.