Fire Door Hinges: Grade 13, Three Hinges and the Mistakes That Fail Inspections
Why hinges matter so much
Hinges carry the whole load of a fire door leaf — often 40–60 kg for FD30 and considerably more for FD60. In a fire they must keep the leaf hung and held tight into the rebate while the door distorts, the intumescent seals expand and the closer keeps pushing. A failed hinge means the leaf drops, the gap opens, and smoke and flame pass. That is why hinges are one of the first things checked on any BS 8214:2026 inspection.
The specification: BS EN 1935 Grade 13
Fire door hinges should be tested and marked to BS EN 1935, and for fire doors the normal requirement is Grade 13 — the highest grade, rated for 200,000 cycles and heavy door leaves. The hinge should carry a CE or UKCA mark and be declared as suitable for use on fire/smoke door assemblies.
Key points:
- Material. Hinges must have a melting point above 800°C, which in practice means steel or stainless steel. Brass and aluminium hinges are not acceptable on a fire door unless specifically tested and certified within the doorset.
- Size. Typically 100 mm × 76 mm × 3 mm for standard FD30 leaves; heavier or wider leaves need correspondingly heavier hinges.
- Number. Three hinges is the standard for a fire door leaf. Heavy, tall or oversized leaves — and many FD60 doors — require a fourth. The doorset certification, not habit, decides.
- Position. The certification will specify hinge positions. A common arrangement places the top hinge near the head, the bottom hinge near the base and the third immediately below the top hinge to resist the leaf's tendency to distort.
Intumescent hinge pads
Many certified doorsets require intumescent pads behind each hinge blade, in the leaf and/or the frame. These expand in a fire to seal the void the hinge recess creates. Whether they are needed depends entirely on the door's fire test evidence — some modern doorsets are tested without them. Removing pads that the certification calls for is a defect; adding pads that were never part of the tested design is also incorrect because it changes the leaf-to-frame relationship.
Screws: the most common failure we find
Hinge screws are the single most frequent hinge defect recorded on inspection. The rules are simple and are broken constantly:
- Every screw hole must be filled. A hinge with two of four screws present is a failure, full stop.
- Screws must be steel and of the length and gauge stated in the installation instructions — normally long enough to reach through the lipping and well into the door core or, in the frame, into the structural opening.
- Screws must be fully driven and countersunk flush so the hinge blade beds tight; a proud screw holds the leaf off the frame and opens the gap.
- No packing. Cardboard, plastic or timber slips behind a hinge blade to "adjust" the door are never acceptable.
Other hinge defects surveyors record
- Binding or dropped leaf — the door catches on the frame or the head gap has closed and the threshold gap opened.
- Worn or noisy bearings on high-traffic doors, causing the leaf to sag out of alignment.
- Mixed hinge types on the same leaf, often from a partial repair.
- Non-fire-rated hinges fitted during unrelated maintenance work.
- Rising butt hinges used as a substitute for a proper self-closing device. A rising butt is not a controlled closing device to BS EN 1154 and does not satisfy the requirement.
- Painted-over hinges, where paint has bridged the knuckle and the door no longer closes freely.
Do fire door hinges need to be self-closing?
No. Closing is the job of a controlled door closer tested to BS EN 1154, either overhead or concealed. The hinge simply has to be strong enough and correctly rated to work with it. A door that only closes because of a spring hinge will normally be recorded as non-compliant on escape routes and in flats.
Getting it right
Changing hinges on a certified fire door is not general joinery. Replacements must match the specification the door was tested with, and the work should be recorded so the doorset's compliance history stays intact. Our fitters carry Grade 13 CE/UKCA-marked hinges, correct-length fixings and intumescent pads, and every remedial is photographed and logged against the door reference.