Access Control on Fire Doors in Alford: Compliant Mag-Locks and Keypads

Can You Fit an Access Control System to a Alford Fire Door?

Yes — but it has to be fail-safe (releases on power loss and on fire alarm activation), it has to be CE-marked and it has to be installed without cutting or modifying the leaf or frame in ways that void the fire test evidence.

On Alford commercial and HMO projects we install access control regularly. Done properly, it does not affect the door's fire rating. Done badly, it turns a certified assembly into a liability.

Fail-Safe vs Fail-Secure

Fail-safe = door unlocks on power loss. This is what fire doors need.

Fail-secure = door remains locked on power loss. Only appropriate for security doors that are not fire doors.

On every Alford fire door install we specify fail-safe mag-locks (typically Assa Abloy, CDVI or Paxton) wired into the fire alarm's Voltage-Free Contact so the door releases automatically on activation.

Common Compliance Errors

  1. Cutting the leaf for a wired lock without intumescent lock protection

  2. Fitting a fail-secure strike where a fail-safe was required

  3. Routing cable through the leaf without a certified cable transfer hinge

  4. Adding a mag-lock that adds so much closing resistance the closer no longer latches the door

What We Fit on Alford Projects

  • Fail-safe mag-locks with EN 1155 hold-open compatibility if required

  • Certified electric strikes protected with intumescent lock kits

  • Cable transfer hinges (Powerlast, Simonswerk) rated to preserve BS 8214

  • Keypad and prox reader wired via first-fix conduit — no leaf modification

  • Fire alarm interface tested and documented as part of handover

Call 01522 775570 to spec a compliant access control solution for your Alford building.